Wize University Physics Textbook (Master) > Thermodynamics
Refrigerators and Heat Pumps

Heat Pumps
- Heat pumps are similar to refrigerators but a heat pump can be used to either heat a system or cool down a system
- The COP (coefficient of performance) for heat pumps is defined as:
COP=∣W∣∣Qdesired∣
Calculate the coefficient of performance (COP) for an air-to-air heat pump to maintain an inside temp of 70°F with an outside temperature of 30°F.
COP = (Thot / Thot - Tcold)
1. Convert the temperatures from Fahrenheit to Celsius:
Th = (70 - 32) x 5/9 = 21°C
Tc = (30 - 32) x 5/9 = -1°C.
2. Convert the Celsius temperatures to Kelvin by adding 273:
Th = 21°C + 273 = 294K
Tc = -1°C + 273 = 272K
3. Plug the temperatures into the formula:
COP = (294K / 294K - 272K) = 294 / 22 = 13.3